ModelC7012G1019
Mounting3/4 inch NPT flange for sight pipe
ApplicationsTypical applications include flame supervision on gas- and oil-fired commercial and industrial burners in Europe, where compliance with German DIN or British Gas Corporation requirements is needed, in conjunction with Honeywell flame safeguard controls using rectification or Ampli-Check flame signal amplifiers.
Key featuresSolid State Purple Peeper ultraviolet flame detector; same as the C7012A except designed to meet BGC (British Gas Corporation) and DIN (German) requirements.; Rated 220 Vac, 50 Hz only, with maximum power consumption of 2.5 watts.; Mounting flange with 3/4 inch NPT internal threads for attaching to a sight pipe; housing is a violet cast-aluminum cover meeting NEMA 4 enclosure requirements.; Protective heat block built into the mounting flange; quartz viewing window rated for 20 psi (138 kPa).; Five NEC Class 1 color-coded leadwires, 8 ft (2.4 m) long, including an additional yellow/green ground wire typical of DIN and BGC designs.; Ultraviolet sensing tube and quartz viewing window are field replaceable.; Ambient operating temperature range of 25°F to 175°F (-4°C to +79°C); weight approximately 1.9 kg (4.25 lb).
Product statusDiscontinued
Product categoryIndustrial combustion safety component - solid-state ultraviolet (UV) flame detector (Solid State Purple Peeper series)
Operating voltage220 Vac, 50 Hz
Power consumption2.5 W maximum
Ambient temperature range25°F to +175°F (-4°C to +79°C)
Viewing window pressure rating20 psi (138 kPa)