ModelC7012E1245
ApplicationsTypical applications include gas, oil or pulverized-coal fired burners and boilers requiring dynamic self-checking flame supervision, including continuously firing burners where the detector and R7247C/R7847C amplifier prove sensing-tube integrity every operating cycle.
Key featuresOscillating shutter interrupts UV reaching the sensor 60 to 120 times per minute to check sensing-tube operation.; Solid-state circuitry consumes 7.0 W maximum.; 120 Vac model, 50/60 Hz.; Ambient operating temperature rating of -20F to 175F (-29C to 79C).; Mounting flange with 3/4 in. NPT internal threads for attaching to a sight pipe.; Quartz viewing window rated for 20 psi (138 kPa); housing meets NEMA 4 enclosure standards.; Six 8 ft (2.4 m) color-coded NEC Class 1 leadwires; field-replaceable sensing tube, window and coil-and-shutter assembly.; Weighs approximately 4.25 lb (1.9 kg); cast case and cover with hot-refractory tube.; SIL 3 capable when used with an R7847C amplifier in a properly designed safety instrumented system.
Product statusDiscontinued
Leadwire length8 ft (2.4 m)
Mounting thread3/4 in. NPT internal
Product categoryIndustrial combustion flame safeguard component - Solid State Purple Peeper ultraviolet (UV) flame detector, dynamic self-checking type
Operating voltage120 Vac, 50/60 Hz
Power consumption7.0 W max
Viewing window pressure20 psi (138 kPa)
Ambient operating temperature-20F to 175F (-29C to 79C)