ModelC7012A1194
ApplicationsTypical applications include gas, oil or pulverized-coal fired burners, boilers and process heaters using Honeywell flame safeguard controls with rectification-type amplifiers, where the detector is mounted on a sight pipe to view the flame root.
Key featuresSolid-state electronic circuitry replaces older vacuum-tube detectors with low power consumption of 2.5 W maximum.; 240 Vac model, 50/60 Hz, per distributor catalogues.; Ambient operating temperature rating of 25F to 175F (-4C to 79C).; Mounting flange with 3/4 in. NPT internal threads for attaching to a sight pipe.; Quartz viewing window rated for 20 psi (138 kPa); a 50 psi window and focusing lens are optional.; Housing meets NEMA 4 enclosure standards with a built-in protective heat block in the mounting flange.; Four 8 ft (2.4 m) color-coded NEC Class 1 leadwires; field-replaceable UV sensing tube and viewing window.; Weighs approximately 4.25 lb (1.9 kg).; Two detectors can be wired in parallel to reduce nuisance shutdowns in difficult sighting applications.
Product statusDiscontinued
Leadwire length8 ft (2.4 m)
Mounting thread3/4 in. NPT internal
Product categoryIndustrial combustion flame safeguard component - Solid State Purple Peeper ultraviolet (UV) flame detector, rectification type
Operating voltage240 Vac, 50/60 Hz
Power consumption2.5 W max
Viewing window pressure20 psi (138 kPa)
Ambient operating temperature25F to 175F (-4C to 79C)