ModelC6097A4410
ApplicationsTypical applications include minimum or maximum gas pressure monitoring in gas trains of forced-draft burners, air pressure and fan monitoring, differential pressure monitoring of filters and air flow, and system leak-tightness checks in boilers and process heating plants.
Key featuresCE certified pursuant to EN 1854; switches on falling pressure (C6097A); hand wheel with mbar scale.; Adjusting range 100 to 500 mbar; mean switching differential 8 to 17 mbar; maximum inlet pressure 600 mbar (withstand pressure).; Deviation from the switching point within plus/minus 15 percent during testing to EN 1854.; Suitable for natural gas, town gas, LPG (gaseous), flue gas, biogas with max 0.1 percent by volume H2S, and air.; Silicone-free NBR diaphragm; housing of glass-fibre reinforced PBT with low gas release; lower housing section AlSi 12.; Switching capacity 24 to 250 V AC, 0.05 to 5 A at cos phi 1; screw terminals; M16 x 1.5 cable gland; protection class IP 65 depending on orientation.; Maximum medium and ambient temperature -20 to +80 deg C; weight 270 to 320 g.
Adjusting range100 to 500 mbar
Product categoryCombustion safety component - diaphragm gas and air pressure switch for burner gas trains, CE certified per EN 1854
Protection classIP 65
Max inlet pressure600 mbar (withstand)
Switching capacity24 to 250 V AC, 0.05 to 5 A (cos phi 1)
Switching differential8 to 17 mbar (mean)
Medium and ambient temperature-20 to +80 deg C