ModelC6097A2110
ApplicationsTypical applications include detecting the upper or lower limit pressure of gas or air supplied to gas burners and detecting clogging of the interlock filter of a burner blower in European gas-fired appliances and heating systems.
Key featuresStand-alone version of the C6097A gas pressure switch; switches on falling pressure.; Operating pressure range 1.0 to 10 mbar; nominal operating differential 0.4 mbar; maximum working pressure 200 mbar.; Set point accuracy within 15 percent of full scale when pressure is increased.; Positive pressure connection Rp 1/4 internal pipe thread (2 x); differential pressure connection Rp 1/8, all to ISO 7-1.; Contact ratings 250 V AC 5 A resistive, 250 V AC 3 A inductive (power factor 0.6); minimum contact current 50 mA at 24 V AC.; NBR single diaphragm; aluminium die-cast housing; PBT case; polycarbonate cover; protection class IP 54.; Ambient temperature -15 to +60 deg C; sensed medium temperature -15 to +80 deg C; plug connection PG11 or three-pin DIN plug.; Conforms to Gas Appliance Directive 90/396/EEC, Low Voltage Directive 73/23/EEC and EMC Directive 89/336/EEC.
Contact rating250 V AC 5 A resistive; 250 V AC 3 A inductive
Product categoryCombustion safety component - diaphragm gas and air pressure switch for burner gas trains (stand-alone version)
Protection classIP 54
Medium temperature-15 to +80 deg C
Ambient temperature-15 to +60 deg C
Pressure connectionRp 1/4 (positive), Rp 1/8 (differential), ISO 7-1
Max working pressure200 mbar
Operating pressure range1.0 to 10 mbar
Nominal operating differential0.4 mbar