Model2108B2001N
ApplicationsTypical applications include offshore platforms, refineries, chemical and gas processing plants, storage and distribution terminals and other hazardous industrial sites requiring continuous flammable hydrocarbon leak detection.
Key featuresMeasuring range 0-100% LEL with a wide selection of hydrocarbon gas and vapour calibrations, including methane, ethane, propane and butane.; 4-20 mA autosensing sink or source output with fault, warning, inhibit and over-range signalling; optional HART over 4-20 mA (version 7) or multidrop Modbus RS485 via DX100(M).; 316 stainless steel construction; ingress protection IP66/67; supply 18-32 VDC (24 VDC nominal); maximum power below 4.5 W.; Fast response, T50 under 3 s and T90 under 4 s for methane; baseline stability within +/- 2% FSD; functional safety SIL 2 per IEC 61508.; Certified for hazardous areas: ATEX II 2 GD Ex d IIC Gb Ex tb IIIC Db, IECEx, and UL/CSA Class 1 Div 1 Groups B, C, D; operating temperature -40 to +65 °C.; Self-compensating optics and absence of moving parts give high reliability with reduced routine maintenance.
Response timeT50 < 3 s, T90 < 4 s (methane)
Signal output4-20 mA (sink or source)
Measuring range0-100% LEL
Product categoryFixed gas detection - point infrared hydrocarbon gas detector (Searchpoint Optima Plus)
Protection classIP66/67
Operating voltage18-32 VDC (24 VDC nominal)