ModelW-MF512C01
Valve classClass A (EN 161)
ApplicationsInstalled as the primary gas control and safety shut-off assembly in Weishaupt gas and dual-fuel burners, including WG20 series models; used in commercial and industrial heating systems and boiler rooms where compact multifunctional gas control with integrated filtration is required.
Key featuresTwo independent normally closed solenoid shut-off valves V1 and V2, Class A per EN 161; DUNGS manufacture for Weishaupt, part number 625003.; Integrated gas microfilter with replaceable insert (DUNGS 605254) for particulate removal upstream of the valve seats.; Maximum operating pressure 500 mbar (50 kPa); threaded union-flange connections Rp 1, 1-1/4, 1-1/2, and 2 inch.; Housing of aluminium and steel; NBR seals and diaphragms; designed for dry, neutral gases including natural gas and LPG.; Ambient temperature -15 to +70 degrees Celsius; dimensions approx. 176 x 114 x 267 mm; weight approx. 6.5 kg.; Solenoid actuation for automatic gas shut-off on burner safety cycles.; Compact pre-assembled design reduces installation space; filter element accessible for servicing.; Vertical or horizontal installation; used in Weishaupt WG20 burners.
Filter insertDUNGS 605254
Connection sizeRp 1, 1-1/4, 1-1/2, 2 inch threaded union flange
Product categoryIndustrial combustion component - multifunctional gas control (Mehrfachstellgeraet) with integrated gas filter, double solenoid valves Class A (Weishaupt OEM version, MF 512 series)
Ambient temperature-15 to +70 °C
Weishaupt part number625003
Max operating pressure500 mbar (50 kPa)