ModelVDK200AS02
ApplicationsTypical applications include gas trains of industrial boilers, forced-draft and premix gas burners, process heating systems, and TRD combustion plants requiring mandatory valve tightness proving before burner operation, used with DUNGS or other EN 161 Class A shut-off valves.
Key featuresValve proving system per EN 1643 for automatic shut-off valves per EN 161 Class A; operates independent of residual inlet pressure.; Maximum operating pressure 360 mbar (36 kPa); test volume range 0.4 l to 20.0 l.; Internal motor pump raises test pressure by 35 to 40 mbar; release time 10 to 26 seconds.; Rated voltage 230 V AC (50 Hz), -15 to +10 percent; approx. 80 VA during pumping, 20 VA in operation.; Degree of protection IP 40; ambient temperature -10 to +60 degrees Celsius; altitude up to 2000 m.; Suitable for gases of families 1, 2 and 3; not for biogas, sewage gas or landfill gas; CE marked.
Release time10 to 26 s
Rated voltage230 V AC, 50 Hz (-15% to +10%)
Product statusDiscontinued
Product categoryIndustrial combustion component - Valve proving system (valve tightness monitoring device) per EN 1643 for automatic gas shut-off valves
Power consumptionapprox. 80 VA (pumping), 20 VA (operation)
Test volume range0.4 l to 20.0 l
Ambient temperature-10 to +60 degrees Celsius
Degree of protectionIP 40
Max operating pressure360 mbar (36 kPa)
Pressure increase by pump35 to 40 mbar