ModelUB500A4
Reset typemanual reset (overpressure lockout)
ApplicationsTypical applications include overpressure safety monitoring and lockout in gas burner trains, industrial boilers, process heating systems, and ventilation installations where a manual-reset pressure limiter is required for high-pressure interlock, preventing automatic restart after an overpressure trip.
Key featuresAdjustable overpressure limiter conforming to EN 1854, class S, with CE, AGA, EAC, UA and UKCA approvals.; Setting range 100 to 500 mbar; maximum operating pressure 600 mbar (60 kPa) for the 500 A4 variant.; Manual reset: switches and locks when set pressure is exceeded, with a glow lamp indicating lock; restart only via the reset button on the setting wheel.; G 1/4 female thread pressure connection per ISO 228; integrated test nipple of 9 mm diameter in the metal housing.; Aluminium die-cast housing, polycarbonate switch components, NBR diaphragms; silver contacts with optional gold-plated for low-voltage DDC.; Degree of protection IP 54 per EN 60529; ambient and medium temperature minus 15 to plus 60 degrees Celsius; storage minus 30 to plus 80 degrees Celsius.; Nominal current AC 10 A; switching voltage AC 10 to 250 V, DC 12 to 48 V.; Suitable for gases of families 1, 2 and 3, air, flue and exhaust gases, and hydrogen.
Order number210970
Setting range100 - 500 mbar
Nominal currentAC 10 A
Product categoryIndustrial combustion component - Adjustable overpressure limiter (pressure switch with manual reset) for gas, air, flue, exhaust gases and hydrogen
Ambient temperature-15 to +60 degrees Celsius
Pressure connectionG 1/4 female thread per ISO 228
Degree of protectionIP 54
Max operating pressure600 mbar (60 kPa)