ModelMB-ZRDLE407B01S50
ApplicationsTypical applications include gas trains of two-stage commercial and industrial burners, modular boilers, and process heating systems requiring combined safety shut-off and pressure regulation in a compact footprint, for small-to-medium capacity burners using natural gas, town gas, or LPG.
Closing time< 1 s
Control typeCommon (V1 and V2 together)
Key featuresTwo-stage function (ZR) with partial volume setting first stage; DLE design with main volume restrictor and adjustable opening behaviour.; DN20 construction size (type 407), V2 double-seat valve; flange connections Rp 1/2 and Rp 3/4 per ISO 7/1.; B01 gas train: one pressure regulator per DIN EN 88 Class A plus two Class A Group 2 valves per DIN EN 161.; S50 variant: V1/V2 common control; outlet pressure range 4-50 mbar; maximum operating pressure 360 mbar (36 kPa).; Microfilter with sieve (NF 50 micrometres); regulator compensated for residual pressure with permanently installed setpoint spring.; Voltage 220-230 V AC 50-60 Hz, 65 VA; IP 54; ambient temperature -15 to +70 degrees Celsius; weight approx 3.4 kg; closing time under 1 second.; Suitable for gases of families 1, 2, 3 and other neutral gaseous media.
Connection sizeRp 1/2 and Rp 3/4 (flange with pipe threads per ISO 7/1)
Nominal diameterDN20
Product categoryIndustrial combustion component - GasMultiBloc combined regulator and two-stage safety shut-off valve
Operating voltage220-230 V AC, 50-60 Hz
Power consumption65 VA
Protection ratingIP 54
Ambient temperature-15 to +70 degrees Celsius
Valve configurationB01 - one regulator + two Class A valves
Outlet pressure range4-50 mbar
Max operating pressure360 mbar (36 kPa)