ModelMB-VEF407B01S10
Net weight3200 g
ApplicationsDesigned for forced-air and premix burners in modulating or two-stage variable modes where precise gas-to-air ratio across the firing range is critical. Used in industrial boilers, process heaters, kilns, and condensing burners. Suitable for natural gas, city gas, LPG in gaseous phase, and other neutral gaseous media of families 1, 2, and 3.
Closing time< 1 s
Key featuresPneumatic gas-air ratio control per EN 12067-1 with adjustable ratio V = pBr/pL from 0.75:1 to 3:1 and zero point correction N; Servo regulator to DIN EN 88-1 Class A Group 2; solenoid valves V1 and V2 to DIN EN 161 Class A Group 2, fast closing and opening; S10 input pressure 5 to 100 mbar; max operating pressure 360 mbar; burner pressure 0.5 to 100 mbar; blower pressure 0.4 to 100 mbar; Flange Rp 1/2 and Rp 3/4 per ISO 7/1; 230 V AC 50-60 Hz; max power 28 VA; IP54; ambient -15 to +70 degrees C; External pulse lines for burner, blower, and firing chamber pressure; closing under 1 s; weight approximately 3.2 kg
Connection sizesRp 1/2, Rp 3/4 (ISO 7/1)
Product categoryIndustrial combustion component - GasMultiBloc with pneumatic gas-air ratio control and double safety shut-off valves (modulating/variable mode)
Protection ratingIP54
Voltage frequency230 V AC, 50-60 Hz
Product dimensionsWidth 74 mm; height 230 mm; depth 151 mm
Ambient temperature-15 to +70 degrees C
Ratio setting rangeV = pBr/pL, 0.75:1 to 3:1
Blower pressure range0.4 to 100 mbar
Burner pressure range0.5 to 100 mbar
Max power consumption28 VA
Max operating pressure360 mbar (36 kPa)
Input pressure range s105 to 100 mbar