ModelMB-DLE420B01S50
Dirt trapTwo-layer microfilter (PreF 50 µm), replaceable without removing the valve
Net weight7800 g
Order code226805
Valve classDIN EN 161 Class A Group 2 (V1 and V2)
ApplicationsUsed in gas trains of atmospheric and forced-draught gas burners in industrial and commercial heating, process heat and steam boiler plants, for natural gas, LPG or town gas (families 1, 2, 3). The common-operation S50 control suits standard single-stage burner applications, while the DN 50 size covers higher-capacity gas throughput.
Key featuresTwo solenoid valves per DIN EN 161 Class A Group 2; V1 fast closing/fast opening, V2 double-seat with main volume restrictor and adjustable slow opening.; S50 variant: V1 and V2 controlled together (common operation) for simple single-stage burner sequencing.; Residual-pressure-compensated regulator per DIN EN 88 Class A Group 2, permanently installed setpoint spring, internal pulse tap.; Inlet up to 360 mbar, outlet 20-50 mbar; Rp 2 (DN 50) flange per ISO 7/1; two-layer microfilter (PreF 50 µm); IP 54; fast closing under 1 s.
Valve controlCommon (V1 and V2 controlled together)
Connection sizeRp 2 (DN 50), flange with pipe threads per ISO 7/1
Regulator classDIN EN 88 Class A Group 2
Valve v2 designDouble-seat valve with main volume restrictor
Product categoryIndustrial combustion component - GasMultiBloc combined gas pressure regulator and double solenoid safety shut-off valve (single-stage)
Opening behaviourFast closing < 1 s; slow opening < 20 s
Operating voltage220-230 V AC, 50-60 Hz
Power consumption80 VA at 230 V AC
Ambient temperature-15 °C to +70 °C
Degree of protectionIP 54
Output pressure range20-50 mbar (2-5 kPa)
Max operating pressure360 mbar (36 kPa)