ModelMB-DLE407B01S22
ApplicationsUsed in single-stage gas burner trains for industrial and commercial heating systems, boilers, kilns, and process burners where compact gas filtration, pressure regulation, and double safety shut-off are required in one fitting. Suitable for natural gas, city gas, LPG (gaseous phase), and other neutral gaseous media of families 1, 2, and 3.
Key features407 size with V2 double-seat valve design; B01 configuration includes two Class A solenoid valves and one pressure regulator; S22 variant: valves V1 and V2 controlled separately; V1 fast-opening, V2 slow-opening with main volume restrictor and hydraulic delay; Output pressure range 4 to 20 mbar; maximum operating pressure 360 mbar (36 kPa); Solenoid valves certified to DIN EN 161 Class A Group 2; regulator to DIN EN 88 Class A Group 2; Flange connections Rp 1/2 and Rp 3/4 with pipe threads per ISO 7/1; voltage 220-230 V AC 50-60 Hz; Protection rating IP54 per EN 60529; interference degree N; ambient temperature -15 to +70 degrees C
Valve v2 typedouble-seat
Opening time v2< 20 s
Connection sizesRp 1/2, Rp 3/4 (ISO 7/1)
Product categoryIndustrial combustion component - GasMultiBloc combined gas pressure regulator and double safety shut-off valve (single-stage function)
Protection ratingIP54
Voltage frequency220-230 V AC, 50-60 Hz
Valve control modeV1 and V2 separately controlled (S22)
Ambient temperature-15 to +70 degrees C
Output pressure range4 to 20 mbar
Max operating pressure360 mbar (36 kPa)