ModelLGW50A2P
ApplicationsTypical applications include differential pressure monitoring in gas burner combustion air supply lines, air proving circuits, ventilation and air-conditioning systems, and flue gas exhaust monitoring where a compact adjustable differential pressure switch with threaded connections and test button is required.
Key featuresAdjustable differential pressure switch conforming to EN 1854, class S, with EC type testing under the EU Gas Appliances Regulation and Pressure Equipment Directive.; Setting range 2.5 to 50 mbar with maximum switching difference of 1 mbar; setting tolerance plus or minus 15 percent of nominal value.; Maximum operating pressure 500 mbar (50 kPa).; A2P variant with G 1/4 tapered female thread for higher pressure, G 1/8 female thread for lower pressure, and integrated test button for safety function checks.; Degree of protection IP 54 per EN 60529; polycarbonate housing and switch components, NBR diaphragms.; Ambient and medium temperature minus 15 to plus 70 degrees Celsius; storage minus 30 to plus 85 degrees Celsius.; Suitable for air, flue and exhaust gases and other non-aggressive gases; not for industrial combustion gases.
Order number272346
Setting range2.5 - 50 mbar
Product categoryIndustrial combustion component - Adjustable differential pressure switch (air pressure switch) for automatic burner controls
Ambient temperature-15 to +70 degrees Celsius
Pressure connectionG 1/4 tapered female thread (high), G 1/8 female thread (low)
Degree of protectionIP 54
Switching differencemax 1 mbar
Max operating pressure500 mbar (50 kPa)