ModelLGW3A2P
ApplicationsTypical applications include differential pressure monitoring in burner air supplies, flue gas and exhaust gas ducts, ventilation systems and air-conditioning plants where periodic functional testing of the safety switch is required by code or maintenance procedure.
Key featuresAdjustable setting range from 0.4 to 3 mbar with a maximum switching difference of 0.3 mbar; setting tolerance plus or minus 15 percent.; Maximum operating pressure 500 mbar (50 kPa); P variant has G 1/4 tapered female thread with integrated test button, 4.6 mm side test point, and G 1/8 female thread for lower pressure.; Integrated test button verifies the safety function by interrupting pressure and releasing diaphragm pressure, changing the microswitch contact state.; Silver (Ag) switching contact with nominal current 10 A AC; optional gold-plated silver (Au) contact for DDC at 24 V DC, 0.01 A.; Polycarbonate housing with IP 54 protection (optional IP 65 hood); NBR diaphragms; ambient and medium temperature from -15 to +70 degrees Celsius.; Pressure switch class S per EN 1854; approved under EC Gas Appliances Regulation and EC Pressure Equipment Directive.
Nominal current10 A AC (Ag contact)
Order no 60pack120204
Order no single272352
Adjustment range0.4 - 3 mbar (field-adjustable)
Product categoryIndustrial combustion component - field-adjustable differential pressure switch with integrated test button for air, flue and exhaust gases (EN 1854 Class S)
Temperature range-15 to +70 degrees C (ambient and medium)
Pressure connectionG 1/4 tapered female thread (+) with test button, 4.6 mm test point, G 1/8 female thread (-)
Degree of protectionIP 54 (optional IP 65)
Switching differencemax. 0.3 mbar
Max operating pressure500 mbar (50 kPa)