ModelLGW3A1
ApplicationsTypical applications include differential pressure monitoring in forced-draft burner air supplies, flue gas and exhaust gas systems, ventilation ducts and air-conditioning plants where a fixed, factory-calibrated trip point is required without field adjustment.
Key featuresFactory-set switching point in the 0.4 to 3 mbar range; not field-adjustable, with a maximum switching difference of 35 Pa.; Maximum operating pressure of 100 mbar (10 kPa); pressure connections via 4.6 mm diameter hose glands.; Silver (Ag) switching contact with nominal current of 10 A AC; optional gold-plated silver (Au) contact for DDC applications at 24 V DC, 0.02 A.; Electrical connection via flat-type connector; optional contact protection covers rated IP 20 or IP 42.; Polycarbonate housing and NBR diaphragms; ambient and medium temperature range from -15 to +85 degrees Celsius.; Approved under EC Gas Appliances Regulation and EC Pressure Equipment Directive; conforms to EN 1854.; Compact design with precise switching action achieved through a frictionless-bearing switching system.
Nominal current10 A AC (Ag contact)
Adjustment range0.4 - 3 mbar (factory-set)
Product categoryIndustrial combustion component - factory-adjusted differential pressure switch for air and non-aggressive gases (EN 1854)
Temperature range-15 to +85 degrees C (ambient and medium)
Pressure connection4.6 mm dia hose gland
Degree of protectionIP 20 or IP 42 (optional contact protection)
Switching differencemax. 35 Pa
Max operating pressure100 mbar (10 kPa)