ModelLGW150A2
ApplicationsTypical applications include differential pressure monitoring across filters, fans and heat exchangers in burner air supply lines, flue gas draught supervision, and ventilation systems where a pressure difference must be converted into a switching signal for burner control or alarm circuits.
Key featuresAdjustable differential pressure switch conforming to EN 1854 class S, CE marked under EU Gas Appliances Regulation and Pressure Equipment Directive.; Setting range 30 to 150 mbar with switching difference 3 mbar maximum and setting tolerance plus or minus 15 percent.; Maximum operating pressure 500 mbar (50 kPa); suitable for air, flue and exhaust gases, not for industrial combustion gases.; Polycarbonate housing with NBR diaphragms; silver contacts, optionally gold-plated for low-energy DC applications.; IP54 protection per EN 60529 (optional IP65); ambient and medium temperature minus 15 to plus 70 degrees Celsius.; Pressure connections via 4.6 mm hose glands; electrical connection via screw terminals with M20x1.5 cable entry or 3-pin plug.
Setting range30 to 150 mbar
Nominal current10 A AC
Product categoryIndustrial combustion component - Adjustable differential pressure switch (for air, flue and exhaust gases)
Protection classIP54 (optional IP65)
Setting toleranceplus or minus 15 percent
Temperature range-15 to +70 degrees Celsius
Pressure connection4.6 mm hose gland
Switching difference3 mbar max.
Max operating pressure500 mbar (50 kPa)