ModelGGW50A4-2
ApplicationsTypical uses include low-range differential pressure monitoring across gas filters, burner air flaps and fans in industrial combustion plants, flue gas draft supervision, and air-to-gas ratio verification. The IP 65 metal housing suits dusty or wash-down environments.
Key featuresSetting range 2.5 to 50 mbar; maximum operating pressure 500 mbar (50 kPa); switching differential delta-p <= 1 mbar.; Metal housing with powder-coated zinc die-cast cover, IP 65 per IEC 529 (EN 60529); integrated test nipple.; Gold-plated silver (Au) contact for DDC at 24 VDC / 0.01 A; nominal AC 10 A at up to 250 VAC; M20 x 1.5 cable gland.; Pressure connections: P+ G 1/4 (ISO 228) on underside, P- G 1/8 (ISO 228).; Ambient and medium temperature -15 C to +70 C; setting tolerance +/-15 percent.; Suitable for gas families 1-3, neutral gases, air, smoke and exhaust gases; no non-ferrous metals; up to 0.1 vol percent dry H2S.; Approved per EN 1854 (class S), EC Gas Appliances Regulation, EC Pressure Equipment Directive; order number 248688.
Order number248688
Setting range2.5-50 mbar
Contact materialGold-plated silver (Au)
Housing materialAluminium die-cast base, zinc die-cast powder-coated cover
Product categoryIndustrial combustion component - Differential pressure switch (positive/overpressure, metal housing version)
Protection classIP 65
Membrane materialNBR
Temperature range-15 C to +70 C (ambient/medium)
Nominal current ac10 A @ up to 250 VAC
Pressure connectionsG 1/4 (+), G 1/8 (-) per ISO 228
Electrical connectionM20 x 1.5 cable gland, screw terminals
Max operating pressure500 mbar (50 kPa)
Max switching differential<= 1 mbar