ModelFRS5100
ConnectionFlange PN 16 per DIN EN 1092-1
ApplicationsInstalled in gas supply lines for industrial burners, boilers, furnaces, and gas equipment requiring stable downstream pressure. The DN 100 flanged size suits medium-to-high flow natural gas, city gas, LPG, and air applications in families 1, 2, and 3. Used where inlet pressure up to 500 mbar must be reduced to a controlled outlet pressure between 2.5 and 200 mbar. The regulator dome may be installed from vertically upright to horizontally lying.
Key featuresDN 100 flanged connection per DIN EN 1092-1 PN 16; Adjustable setpoint spring; standard blue spring covers 10 to 30 mbar outlet range; Inlet pressure compensation diaphragms and safety diaphragms for overpressure protection; Internal pulse tap for outlet pressure as standard; external pulse connection optional on both sides; Max operating pressure 500 mbar; outlet pressure adjustable 2.5 to 200 mbar via spring selection; No non-ferrous metals in gas-conveying parts; suitable for gases with up to 0.1 vol percent H2S
Standard springBlue, 10-30 mbar
Housing materialAluminium, steel
Nominal diameterDN 100 (flanged)
Product categoryGas Pressure Regulator / Flanged Pressure Regulator
Seals diaphragmsNBR
Ambient temperature-15 C to +70 C
Inlet pressure range+5 mbar or p2+2.5 mbar up to 500 mbar
Outlet pressure range2.5 mbar to 200 mbar (spring-dependent)
Max operating pressure500 mbar (50 kPa)
Order number internal pulse082 552